Why am I unable to access the web browser of a TM3BCEIP?
If you can ping the IP address 90.0.0.1 or the modules IP address, try the below.

Use the Edge browser with the following settings: Edge browser > Settings > Default browser > Allow IE Mode > Add pages http://90.0.0.1/ & https://90.0.0.1/
(use the IP address of the module instead of 90.0.0.1 if using ethernet instead of usb)

Restart Edge and connect to the modules web browser.

Upgrade firmware to 2.6.1.0 or higher and the above will no longer be necessary.