The power to the M172 should be turned off ( no connections to the USB mini port for programming )
Then insert the USB stick and then apply power.
At boot-up the M172 will detect the USB memory stick and will copy the project from the USB device into the PLC.
When the copy process is finished only the Green LED on the M172 will be lit.
Remove USB memory stick and then power cycle the M172 PLC.
The new program will begin operating.
This process was successful and the M172 PLC is operational.
Released for:Schneider Electric New Zealand
The power to the M172 should be turned off ( no connections to the USB mini port for programming )
Then insert the USB stick and then apply power.
At boot-up the M172 will detect the USB memory stick and will copy the project from the USB device into the PLC.
When the copy process is finished only the Green LED on the M172 will be lit.
Remove USB memory stick and then power cycle the M172 PLC.
The new program will begin operating.
This process was successful and the M172 PLC is operational.