{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

How to establish communication between the programming computer loaded with PL7-Pro and TSX37 or TSX Nano slave via Uni-Telway Bus.

To communicate between PL7-Pro loaded in the programming computer and TSX37 master via Uni-Telway bus, the 'SYS' (system) address must be entered in PL7 Pro.

Note: A sufficient number of addresses must be configured in the master and addresses 1, 2 and 3 must be reserved for PL7 Pro.

To communicate between PL7-07 and TSX Nano slave via Uni-Telway bus, address 0.254.5.254.10'x' must be entered in PL7-07, where 'x' is the TSX Nano slave address.

Schneider Electric Philippines

Explore more
Range:
PL7
Explore more
Range:
PL7
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.