Pesquisar nas perguntas frequentes (FAQ)
Why do I have NaN values for PowerTag NSX 3P ?
If you are using a 3P PowerTag NSX on a 3P+N system please check that:
- you have connected the white wire to the Neutral of your panel
- the Electrical Network System is defined as 3PH4W under your Smartlink or PowerTag Link Web Interface
Publicado para:Schneider Electric Portugal
Explorar mais
Gama:
Explorar mais
Gama: