Control wiring considerations when replacing an ATV66 with a ATV61/71
Product Line:
Altivar 66
Environment:
All releases
Cause:
Replacing drives.
Resolution:
When converting the wiring to the Altivar 61/71 drive, discard the wires on CL1 and CL2 (ATV66) , not used on the ATV61/71.
Also the run permissive and run forward are swapped around, between the ATV66 and ATV61/71.
ATV66: LI1 = run permissive and LI2 = run forward
ATV61/71: LI1 = run forward and LI2 = run permissive (nSt) (run permissive, if used assign freewheel stop nSt (Fun Menu 1.7) to LI2))
Most other terminations will be the same.
Released for: Schneider Electric Saudi Arabia
Control wiring considerations when replacing an ATV66 with a ATV61/71
Product Line:
Altivar 66
Environment:
All releases
Cause:
Replacing drives.
Resolution:
When converting the wiring to the Altivar 61/71 drive, discard the wires on CL1 and CL2 (ATV66) , not used on the ATV61/71.
Also the run permissive and run forward are swapped around, between the ATV66 and ATV61/71.
ATV66: LI1 = run permissive and LI2 = run forward
ATV61/71: LI1 = run forward and LI2 = run permissive (nSt) (run permissive, if used assign freewheel stop nSt (Fun Menu 1.7) to LI2))
Most other terminations will be the same.
Released for: Schneider Electric Saudi Arabia








Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.