Issue
M580 CPU SMTP capability
Product Line
M580
Environment
Unity Pro, Control Expert
Resolution
The M580 CPU does not have SMTP capability. Therefore, there is no Send_Email functionality like the M340 CPU .
The M580 CPUs do support the MBP_MSTR and L9_MSTR block. However, for the MBP_MSTR function block, the M580 CPUs only support the following operation codes: 1 = Write data, 2 = Read data, 14 = CIP Explicit Message, 15 = Send Modbus Request, 23 = Read / Write data.
The SMTP protocol is included in CTRL NOC (BMENOC0321). From the user manual, based on predefined events or conditions, messages are created using the DATA_EXCH function block.
This will be the SMTP solution available for M580.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
M580 CPU SMTP capability
Product Line
M580
Environment
Unity Pro, Control Expert
Resolution
The M580 CPU does not have SMTP capability. Therefore, there is no Send_Email functionality like the M340 CPU .
The M580 CPUs do support the MBP_MSTR and L9_MSTR block. However, for the MBP_MSTR function block, the M580 CPUs only support the following operation codes: 1 = Write data, 2 = Read data, 14 = CIP Explicit Message, 15 = Send Modbus Request, 23 = Read / Write data.
The SMTP protocol is included in CTRL NOC (BMENOC0321). From the user manual, based on predefined events or conditions, messages are created using the DATA_EXCH function block.
This will be the SMTP solution available for M580.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)