Why Smartlink SI-D and SI-B are displaying negative power for PowerTag M63, P63, F63 ?

Article available in these languages: Spanish

This issue appears with Smartlink SI-B and SI-D firmware version older than 2.2.7.

Please upgrade the Firmware of your Smartlink with the latest version of EcoStruxure Power Commission.