Is there any method to remove disturbance record and events from Micom P40 relay?

Issue:
Method to remove disturbance and events from Micom P40 relay

Environment/Product line:
Easergy P3 relay

Resolution:
Removing the Battery will erase the disturbance records and events when the device will be powered Off.

To delete the disturbance records and events, please remove the battery and power Off the Micom relay during one minute.

Before powering Off the Micom relay, you need to take care to avoid having a maltrip and you need also having a backup protection.

Please note that removing the battery will not erase the settings.