{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

What can cause the 4-20mA signal to latch at 20mA on the ATV61 or Eflex drives?

Issue:
4- 20mA signal is stuck and will not clear on ATV61 or Eflex.

Product Line:
Altivar ATV61 Eflex

Environment:
All

Cause:
Noise issues

Resolution:
A voltage surge or spike on the mA input exceeding 7.9 V on this input will cause the analog input to jump to 20 mA and to stay there until power is cycled.
If the voltage surge/spike can't be eliminated by proper cable routing and shielding, or through the use of an isolator you can install a 6.8 V zener diode (available at most electronic stores) to prevent the excess voltage from reaching the AI2 input.
Put the cathode end (marked with a line) on the AI2 input, and the other end on the COM terminal.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Altivar 61Altivar 71Altivar 71 PlusAltivar 61 PlusAltivar AFE (Active Front End)
Utforska mer
Produktfamilj
Altivar 61Altivar 71Altivar 71 PlusAltivar 61 PlusAltivar AFE (Active Front End)