{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

Implementing CIP Explicite messaging to Modbus object between a 140NOC78000 (client) and a 140NOC78000 (server)

Issue
When using the 140NOC78000 as a server, to get process data through the Modbus object, only Unconnected_ Send messaging will work. The attachment is an example on how to perform an Explicit messaging using the MBP_MSTR block from a 140NOC78000 client.


Product Line
Quantum
140NOC78000


Environment


Resolution
Using UCMM and connected messaging will only return diagnostic data when communicating to a 140NOC78000

Schneider Electric Sverige

Bilagor

140NOC78000_CIP_Modbus_Object_Read.ppt140NOC78000_CIP_Modbus_Object_Read.ppt [308 KB]
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj