{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

I am getting "Cannot create task" error during startup of Runtime Project and I/O Server stops PowerScada version 7.20 SP1.

I am getting "Cannot create task" error during startup of Runtime Project and I/O Server stops.
This is caused by duplicate IO Device names. This can be verified by reviewing the IO Device names in Units database, if duplicates exist either rename them or delete the unwanted device.


Legacy KB System (APS) Data: RESL211126 V1.0, Originally authored by RaDe on 04/04/2013, Last Edited by RaDe on 04/04/2013
Related ranges: PowerSCADA Expert 7.2

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj