Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

Can a single meter monitor both sides of an isolated transformer and retain isolation?

Product Line
PowerLogic Meters
ION Meters

Environment
Monitoring

Resolution
No, a single meter can only monitor a single point. Accurate measurements require Vref, so isolation would be lost if both sides of the transformer were connected to it.