What needs to be done to use Blokset at high altitudes (2000m, 3000m, etc.)?

It is possible to use BlokSeT at higher altitude >2000m. We have to apply the derating value as informed in the latest BlokSeT catalog.

As per the table below, derating to be applied for circuit breaker and rated voltage.

Altitude derating

Schneider Electric Sverige

What needs to be done to use Blokset at high altitudes (2000m, 3000m, etc.)?

It is possible to use BlokSeT at higher altitude >2000m. We have to apply the derating value as informed in the latest BlokSeT catalog. 

As per the table below, derating to be applied for circuit breaker and rated voltage.

Altitude derating