When using the HMI for speed control on the ATV61 or ATV71 drives can the drive run faster than the programmed high speed settings?
Issue:
Operating the drive in Local mode, the dial allows the speed reference to be adjusted above the 60Hz of High Speed value.

Product Line:
ATV71 Altivar 71

Environment:
All ATV61 and ATV71 drives

Cause:
Installation / Setup

Resolution:
The drive will not operate faster than the programmed high speed.  The HMI reference can be adjusted above the high speed parameter, but the drive will not actually operate beyond the high speed setting.

Schneider Electric Sverige

When using the HMI for speed control on the ATV61 or ATV71 drives can the drive run faster than the programmed high speed settings?
Issue:
Operating the drive in Local mode, the dial allows the speed reference to be adjusted above the 60Hz of High Speed value. 

Product Line:
ATV71 Altivar 71

Environment:
All ATV61 and ATV71 drives
 
Cause:
 Installation / Setup

Resolution:
The drive will not operate faster than the programmed high speed.  The HMI reference can be adjusted above the high speed parameter, but the drive will not actually operate beyond the high speed setting.

Schneider Electric Sverige

move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.