Can I use the service port on the M580 HSBY processor for SCADA traffic while servicing ERIO ?
Not recommended. Please consider using an NOC module. The service port does not support Rapid Spanning Tree Protocol and as a result the connection of each of these ports to a SCADA can result in an excessive amount of broadcast or ARP traffic.

We recommend using the NOC option module for SCADA in HSBY applications.

Schneider Electric Sverige

Can I use the service port on the M580 HSBY processor for SCADA traffic while servicing ERIO ?
 Not recommended. Please consider using an NOC module. The service port does not support Rapid Spanning Tree Protocol and as a result the connection of each of these ports to a SCADA can result in an excessive amount of broadcast or ARP traffic. 

 We recommend using the NOC option module for SCADA in HSBY applications.

 

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.