{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.
Hur kan vi hjälpa dig idag?
The 4202-DR or 4202-DS flashes S6 ERROR (5G, SG or 56) and then the display goes blank.

This is a normal part of the boot up sequence when there is no flow computer C program installed. This will happen after a cold boot or if the RAM battery has failed and it has lost it's C program.

You will need to connect to the 4202 with RealFLO, install a flow computer and a configuration that has elements setup for the Display Module. The Display Module depends on how the flow computer is configured so if nothing is configured, it won't display anything.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Artiklar som kan vara till nytta
Utforska mer
Produktfamilj