Can a 63.75" tall PDU be installed into a 38U NetShelter CX cabinet?

Issue:
The 63.75" tall PDU does not fit onto the accessory rail. Will it fit anywhere else inside the cabinet?

Product Line:
NetShelter CX

Environment:
AR4038A, AR4038IA

Cause:
One of the 63.75" tall PDUs has been specc'd into a 38U NetShelter CX cabinet.

Resolution:
Yes, the 63.75" tall PDUs can attach to the rear mounting rail. Please see the attached file for mounting instructions.

Schneider Electric Sverige

Bilagor

20160729 Tall PDU Mounting Into 38U NetShelter CX.docx20160729 Tall PDU Mounting Into 38U NetShelter CX.docx [5.95 MB]