{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

What can cause an ETHF embedded ethernet com interrupt fault on the ATV630 and ATV930 process drives?

Issue:
Getting a ETHF embedded ethernet com interrupt fault on the ATV630 and ATV930 process drives.

Product Line:
ATV630 and ATV930 drive

Environment:
All with built in Ethernet

Cause:
Communication interruption on the Ethernet ModbusTCP bus.

Resolution:
Keep in mind that if the PLC or controller is not writing a command or reference to the drive within the programmed TTOB (Ethernet timeout or Hold up time) the Drive can trip on ETHF fault.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Altivar Process ATV600Altivar Process ATV900
Utforska mer
Produktfamilj
Altivar Process ATV600Altivar Process ATV900