With a SCADAPack 575 What Does the Message "This isn't a valid PLC Address, or PLC is busy, or media is off" mean?
When using a SCADAPack 575 and attempting to connect the logic debugger if the message "This isn't a valid PLC Address, or PLC is busy, or media is off" is displayed it can mean that the Logic Debugger service is not enabled in the rPAC.

To remedy this:
  1. Return to RemoteConnect
  2. Open the offline configuration
  3. In the "SCADAPack x70 Logic" section enable the "Logic Debugger Service"
  4. Download the configuration again.

Schneider Electric Sverige

With a SCADAPack 575 What Does the Message "This isn't a valid PLC Address, or PLC is busy, or media is off" mean?
When using a SCADAPack 575 and attempting to connect the logic debugger if the message "This isn't a valid PLC Address, or PLC is busy, or media is off" is displayed it can mean that the Logic Debugger service is not enabled in the rPAC.

To remedy this:
  1. Return to RemoteConnect
  2. Open the offline configuration
  3. In the "SCADAPack x70 Logic" section enable the "Logic Debugger Service"
  4. Download the configuration again.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.