Does LC1D80BD have internal bi-directional diode?

Issue:
LC1D80 and LC1D95 bi-directional diode

Product Line:
TeSys™ D Contactors

Environment:
Contactor Accessories

Resolution:
LC1D80 and LC1D95 does not have an internal bi-directional peak limiting diode on their DC coils. LA4DC3U (Screw connection of wire to the contactor coil terminals 24–250 Vdc, 3p-4p) must be ordered separately.

The LC1D09 to LC1D38 have an internal diode by default on their DC coils.