{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

How to know the absence of x80 IO in local M580 rack when it is configured as Device DDT ?

1.Issue

How to know the absence of x80 IO in local M580 rack when it is configured as Device DDT ?

2.Environment

M580 series ,X80

3.Resolution

The detail diagnostics status of x80 IO could be accessed by implementing READ_STS_MX.
Here are two samples to get status for digital and analog modules.


When COM_FLT is set to 1 ,it means the module could not be detected by CPU and module would be absent in the rack.

Schneider Electric Sverige

Bilagor

read_sts.zipread_sts.zip [54.48 KB]
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj