{}

Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.

Sök bland vanliga frågor (FAQ)

What is the method of phase imbalance detection and tripping in TeSys Giga OLR?

Tripping signal shall be sent by phase imbalance protection when detecting imbalance ratio is above 40%. And phase imbalance trip time is 5s(with tolerance ± 20%).
The definitions of phase imbalance ratio and average current according to Annex T T.5.5 IEC60947-1.

Schneider Electric Sverige

Utforska mer
Produktfamilj
TeSys Giga protection relays
Utforska mer
Produktfamilj
TeSys Giga protection relays