{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

How to deactivate the Earth Fault protection in Micrologic 6.0 trip unit of Masterpact ACB.

Article available in these languages: Finnish, French, Dutch

To deactivate the Earth Fault protection function in Micrologic 6.0 trip unit, follow the below procedure:

1. On the Masterpact Air Circuit Breaker (ACB), you have to put the jumpers in between F1-M1 and M2-M3 terminals.
2. Remove the External Sensor from the busbars and disconnect the wiring between Sensor and the ACB.
In case External sensor can't be removed from the busbars then remove the wires between Sensor and ACB. Next jumper the sensor terminals T1-T2 and T3-T4.
Refer the attached document describing the procedure.

Schneider Electric Singapore

Attachment(s)

Deactivate Ground fault Protection.pdfDeactivate Ground fault Protection.pdf [6.65 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: