{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What needs to be done when prompted PrtF Fault on ATV61 display after installing replacement MCB and/or Power Board?

Issue:
ATV61 Drive Shows PrtF Fault after replacing MCB and/or Power Board.

Product Line:
Altivar 61

Environment:
All

Cause:
Altivar 61 with PrtF Fault

Resolution:
Need to Hit Enter, select Power ID (For 18-Pulse CPD=IP00, E-Flex =IP00, MCC = IP00,M-Flex =IP00, Open or Custom Enclosed units = IP20, etc.) Set for IPxx and hold Ent key for 2 seconds.

Schneider Electric Singapore

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: