{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

How to resolve a Webclient deployment error: "Method Not Allowed" In PLScada 7.10, PowerScada Expert 7.2 or 7.3.

If you are trying to setup your deployment and you get to the deployment page you are seeing the error "Method Not Allowed" on the top right, this means that the issue is with your IIS setup. Please refer the manual below to verify your IIS setup or follow KB article RESL5816.
Web Client - Quick Start 7.20.pdf


Legacy KB System (APS) Data: RESL211642 V1.0, Originally authored by RaDe on 06/03/2013, Last Edited by RaDe on 06/03/2013
Related ranges: PowerLogic SCADA 7.1, PowerSCADA Expert 7.3, PowerSCADA Expert 7.2

Schneider Electric Singapore

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: