How to configure ATS22 to test an unloaded motor?

Issue:
Can an unloaded motor be tested with an ATS22 Softstarter?

Product Line:
Altistart 22

Environment:
Shop tests, unloaded motor

Cause:
Testing the ATS with an unloaded motor, usually trips the ATS22 with SSCr.

Resolution:
Yes.
After entering the correct motor data, set the following parameters:

- LAC = ON
- t90 =  Factory 30 change to 10. ( Due to No Load connected and monitor ramp acceleration. This value to be changed back or increased when in the field under actual start-up )
- ILt =    Factor 350 change to 200% for Shop Testing. ( Value to be changed in the field if Current Limit trips out )
- tLS =   Factory 15s change to 60s for Shop Testing. ( Changed back to 15s after completion of testing )
- ACC = Factory 10s change to 60s for Shop Testing. ( Changed back to 10s after completion of testing )
- SSC = Factory On, changed to oFF. ( Using Voltage control vs. Torque )
- ItH =   On. ( Factory is On)

Schneider Electric Singapore

How to configure ATS22 to test an unloaded motor?

Issue:
Can an unloaded motor be tested with an ATS22 Softstarter?

Product Line:
Altistart 22

Environment:
Shop tests, unloaded motor

Cause:
Testing the ATS with an unloaded motor, usually trips the ATS22 with SSCr.

Resolution:
Yes.
After entering the correct motor data, set the following parameters:

- LAC = ON
 - t90 =  Factory 30 change to 10. ( Due to No Load connected and monitor ramp acceleration. This value to be changed back or increased when in the field under actual start-up )
- ILt =    Factor 350 change to 200% for Shop Testing. ( Value to be changed in the field if Current Limit trips out )
- tLS =   Factory 15s change to 60s for Shop Testing. ( Changed back to 15s after completion of testing )
- ACC = Factory 10s change to 60s for Shop Testing. ( Changed back to 10s after completion of testing )
- SSC = Factory On, changed to oFF. ( Using Voltage control vs. Torque )
- ItH =   On. ( Factory is On)

Schneider Electric Singapore

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.