Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is the minimum voltage rating for DC Bus fuses on Altivar drives?

Article available in these languages: Spanish

Issue:
What is the min voltage rating for DC Bus fuses?

Product line:
ATV71, ATV312, ATV320, ATV930

Environment:
All

Cause:
Power is supplied directly to the Altivar DC bus and fuse protection is recommended.

Resolution:
With Line supply voltage of 230-400Vac, use 690Vdc rated fuses.
With Line supply voltage of 440-480Vac, use 800Vdc rated fuses.
With Line supply voltage of 500-690Vac, use 1000Vdc rated fuses.