Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Do you recommend non-shielded cable over shielded cable for longer drive to motor leads?

Issue:
Is shielded or non-shielded cable recommended for longer motor leads?

Product Line:
Altivar drives

Environment:
All model numbers

Cause:
N/A

Resolution:
A shielded cable will have more stray capacitance to ground as compared to a non-shielded cable.
So the longer the shielded cable the more leakage current that can occur to ground.
This leakage current can cause nuisance ground detection faults.