{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

How to setup a run status on an ATS22 softstart?

Article available in these languages: Spanish

Issue:
ATS22 run status setup

Product Line:
Altistart 22

Environment:
All

Cause:
Run status

Resolution:
Go into I/O menu.
Find R1 relay parameter.
R1 can be used as a run status.
R1 can be programmd to the following:
NSTP - starting - Relay is not energized at stop and is energized at all other times.
Run - running - Relay is energized when the bypass contactor is closed

Schneider Electric Singapore

Explore more
Range:
Altistart 22
Explore more
Range:
Altistart 22
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.