{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vitajte na webovej lokalite spoločnosti Schneider Electric

Vitajte na našej webstránke.

Prehľadávať FAQ

What can be the reason of service alarm on ATV212?

Drive service alarm (can be assigned to relay output signalization) may stand for recommendation for cooling fan replacement, main control board lifetime, DC bus capacitors lifetime or high operation time.
Drive service alarm (lifetime) is influenced by parameter F634. Exact type of this service alarm can be identified in monitoring menu - see highlight in enclosed ATV212 manual  extract.

Schneider Electric Slovakia

Príloha(-y)

Extracted pages from ATV212_programming_manual_EN_S1A53838_03_1.pdfExtracted pages from ATV212_programming_manual_EN_S1A53838_03_1.pdf [185.39 KB]
Objavte viac
Rad:
Altivar 212
Objavte viac
Rad:
Altivar 212