Prehľadávať FAQ
SELV and Non-SELV signal wires size and specifications
Product line:
Three Phase UPS, Galaxy V Series
Environment:
GVS, GVM, GVL, GVX
Resolution:
All Class 2/SELV signal cables shall be double insulated/jacket cable and minimum rated for 30 VDC. All non-Class 2/non-SELV signal cables shall be double insulated/jacket cable and minimum rated for 600 VAC.
Three Phase UPS, Galaxy V Series
Environment:
GVS, GVM, GVL, GVX
Resolution:
All Class 2/SELV signal cables shall be double insulated/jacket cable and minimum rated for 30 VDC. All non-Class 2/non-SELV signal cables shall be double insulated/jacket cable and minimum rated for 600 VAC.
Publikované pre:Schneider Electric Slovakia
Objavte viac
Rad:
Objavte viac
Rad: