HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
1. Install this product in accordance with National Wiring Regulation. Failure to follow these instructions will result in death or serious injury.
HAZARD OF IMPROPER OPERATION
2 . Feed only the QOvs RCBO from the bottom. Failure to follow these instructions can result in equipment damage
3. The Installation, or part of it, is protected by devices that automatically switch off the supply if an earth fault develops. These devices should be tested periodically according to the local regulations, by pressing on the button marked "T".
The devices should switch off the supply immediately and should then be switched on to restore the supply.If the devices do not switch off the supply when the button is pressed, seek expert advice.
HAZARD OF IMPROPER OPERATION
Do not use the Test Button to switch OFF RCBO. Failure to follow these instructions can result in equipment damage.
Periodic test:
In the absence of any regulation, Schneider Electric recommends the test should be carried out once a month.
Megger test:
QOvs RCBO must be disconnected before any dielectric tests are carried out.