Issue
To inform users the byte order of MBP_MSTR "Get Local Statistics" Board Status for different 140NOE77101/11 and 140NOE77100/10 versions and which order will be consistently used for future product releases.
Product Line
EcoStruxure Control Expert (former Unity Pro), Modicon Quantum
Environment
140NOE77101
Resolution​​​​​
To inform users the byte order of MBP_MSTR "Get Local Statistics" Board Status for different 140NOE77101/11 and 140NOE77100/10 versions and which order will be consistently used for future product releases.
Product Line
EcoStruxure Control Expert (former Unity Pro), Modicon Quantum
Environment
140NOE77101
Resolution​​​​​
1. 140NOE77111/01 & 140NOE77100/10 MBP_MSTR Get local statistics Word3 board status:
140NOE77111/01 V2.0, V3.0, V3.1, V3.3, V3.6 & 140NOE77100/10 V3.0, V3.3, V3.4 has the same order as the table below:
140NOE77111/01 V2.0, V3.0, V3.1, V3.3, V3.6 & 140NOE77100/10 V3.0, V3.3, V3.4 has the same order as the table below:
Bit # | Definition |
15 | 0=link LED off; 1= Link LED on |
14 | 0=Application LED off; 1= Application LED on |
13 | 0=twisted pair; 1=fiber |
12 | 0=10Mbit; 1=100Mbit |
11... 8 | Reserved |
7... 4 | Module Type |
3 | Reserved |
2 | 0=half duplex; 1=full duplex |
1 | 0=not configured; 1=configured |
0 | 0=PLC not running; 1=PLC/NOE running |
NOTE: Bit 0 is a low bit counting from right side, so that means: PLC Running = 0x0001, Application LED = 0x4000, LED connection = 0x8000.
140NOE77111/01 V3.5 & 140NOE77100/10 V1.02, V2.0 has the same order as the table below:
Bit # | Definition |
15...12 | Module Type |
11 | Reserved |
10 | 0=half duplex; 1=full duplex |
9 | 0=not configured; 1=configured |
8 | 0=PLC not running; 1=PLC/NOE running |
7 | 0=link LED off; 1= Link LED on |
6 | 0=Application LED off; 1= Application LED on |
5 | 0=twisted pair; 1=fiber |
4 | 0=10Mbit; 1=100Mbit |
3...0 | Reserved |
NOTE: Bit 0 is a low bit counting from right side, so that means: PLC Running = 0x0100, Application LED = 0x0040 , LED connection = 0x0080.
2. Documentation Mismatch:
· Unity V2.2 and Concept V2.2, V2.6 help file uses the same byte order as table 1.
· Modicon Quantum with Unity Ethernet Network Modules User Manual (6/2006) and Transparent Ready User Guide (10/2005) use the same byte order as table 2.
We have swapped MBP_MSTR Get local statistics Word3 board status byte order when we released certain firmware versions. This also causes the product user manual, and Unity, Concept Help file board status