{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Is there single phase contactor available for AC3 application?

There is not a  single phase contactor for AC3 application. However you can use LC1D contactor.
When using a TeSys overload relay which has single phase sensitivity, the overload must be wired to electrically defeat this feature.  If any of the bimetals are left unpowered the overload will eventually trip.
The power wiring shown below is for 240VAC (single phase)

Contactor

Schneider Electric Thailand

Related products for Schneider Electric Thailand
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Related products for Schneider Electric Thailand
Range: