Symmetra PX 250/500: What happens when EPO is activated?
Issue:
Symmetra PX 250/500; What does the EPO (Emergency Power Off) trip
Product line:
Symmetra PX 250/500
Environment:
All serial numbers
Cause:
What occurs when the EPO on a Symmetra PX 250/500 button is engaged?
Resolution:
When the EPO is activated, UPS output breaker Q2 and the battery breakers are tripped. The Power Modules (inverter), and if in Static Bypass operation, the UPS  will turn off.