{}

Markalar

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
SSS'leri Arayın
How does one read the actual torque in the Lexium drive via an analog signal output?

Issue
How does one read the actual torque in the Lexium drive via an analog signal output?

Product Line
Lexium Drives

Resolution
You may configure the Lexium analog output to output the actual current (ANOUTx = 2; 10 V = IPEAK).
Read the output analog voltage value from the output pin and multiply the read value by the motor's torque constant value to calculate the actual torque.

t = i * Kt

Where :
t = torque
i = actual current
Kt = torque constant of the motor

Also note: the Lexium analog output has a resolution of 10 bits

Schneider Electric Turkey

Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Yardımcı olabilecek makaleler
Schneider Electric Türkiye ile İlgili Ürünler
Seri: