How can the ATV12 be set back to factory default settings?

Issue:
Can I reset the ATV12 drive back to factory default settings?

Product Line:
Altivar ATV12

Environment:
All

Cause:
Clear out old program and reset back to factory default.

Resolution:
From RDY, press Enter
Scroll to CONF, press Enter
Scroll to FCS, press Enter
Choose iNi and hold Enter down for 3 seconds
This will reset the drive back to its original factory settings.