Easypact MVS / CVS is not tested in BlokSeT because,
- The dimension and mounting of the MVS / CVS is exactly identical to NW or MTZ / NSX.
- Thermal characteristics, power loss and current path of MVS / CVS is same with the tested design of NW or MTZ / NSX.
- The short circuit rating of the MVS / CVS is less than Blokset Icw
Yayımlanma amacı:Schneider Electric Turkey

