Video: How to download Advantys island configuration (STB NIP xxxx) through TCP/IP ?

Follow these steps to download Advantys island configuration (STB NIP xxxx) through TCP/IP :


1. Open the Advantys configuration software and browse the configuration backup and open it
2. RIght click on island name and build the configuration
3. Go to online > Connection settings
4. Select the connection type as TCP/IP and enter the IP address of the Advantys STB NIP xxxx module
5. Go to online > Click connect > Click on download option to start the download