{}

Markalar

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
SSS'leri Arayın
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
Issue
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
image.png
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
  1. Delete the content of Standby IO Server Name column or configure correct IO Server name in equipment.csv file. and save it.
image.png
  1. Make sure the package received from EPAS-E contains only one OIS HMI and not multiple HMI as below.
image.png

Schneider Electric Turkey

Schneider Electric Türkiye ile İlgili Ürünler
Ürün:
Yardımcı olabilecek makaleler
Schneider Electric Türkiye ile İlgili Ürünler
Ürün: