What could trigger an ObF2 error on ATV680 enclosed AFE drives?

Issue:

AFE bus unbalancing or ObF2 fault on the ATV680 Drives.

Product Line:

ATV680 and ATV980 enclosed drives with AFE

Environment:

All 680 and 980 AFE Drives only

Cause:

The Drives internal DC bus voltage is out of range from unsymmetric mains voltage or inoperative AFE Brick.

Resolution:

-Turn off stop and go feature and see if the drive powers up.

-Analysis mains voltage and DC bus voltage.

-Perform visual on the AFE brick (Requires Field Services onsite)

-Replace the AFE brick (Requires Field Services onsite)

Note to turn off stop and go feature from the HMI or keypad.

-Main menu

-My Preferences

-Stop and go

Set to NO

Schneider Electric Turkey

What could trigger an ObF2 error on ATV680 enclosed AFE drives?

Issue:

AFE bus unbalancing or ObF2 fault on the ATV680 Drives.

 

Product Line:

ATV680 and ATV980 enclosed drives with AFE

 

Environment:

All 680 and 980 AFE Drives only

 

Cause:

The Drives internal DC bus voltage is out of range from unsymmetric mains voltage or inoperative AFE Brick.

 

Resolution:

-Turn off stop and go feature and see if the drive powers up.

-Analysis mains voltage and DC bus voltage.

-Perform visual on the AFE brick (Requires Field Services onsite)

-Replace the AFE brick (Requires Field Services onsite)

 

Note to turn off stop and go feature from the HMI or keypad.

-Main menu

-My Preferences

-Stop and go

Set to NO

Schneider Electric Turkey

Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Schneider Electric Türkiye ile İlgili Ürünler
Seri:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.