What is the ATS48 soft starters dissipated watts loss for calculating heat loss for enclosure sizing?
Issue:
Looking for the watts loss on a  ATS48 soft start

Product Line:
Altistart ATS48 soft starters

Environment:
All

Cause:
Needs to know the dissipated heat loss in watts the ATS48 soft starter will produce when running at full load.

Resolution:
See the table below and choose the ATS48's watt loss based on if a shorting contactor is being used or not.


ATS48 Watts Loss