搜尋常見問題
Why will the KC breakers not fit into the HCM interior?
Issue:
HCM interior cannot take KC circuit breakers
Product Line:
Panelboard, Circuit Breakers
Environment:
ILine Panelboard and Circuit Breakers
Resolution:
Size wise the KC will fit. However, the KC breaker needs a vented trim to allow the gases to escape on a high level fault. The HCM trim is not vented. But the Powerpact JJ and JL do not need the vented trim so they can be used.
HCM interior cannot take KC circuit breakers
Product Line:
Panelboard, Circuit Breakers
Environment:
ILine Panelboard and Circuit Breakers
Resolution:
Size wise the KC will fit. However, the KC breaker needs a vented trim to allow the gases to escape on a high level fault. The HCM trim is not vented. But the Powerpact JJ and JL do not need the vented trim so they can be used.
發佈於:施耐德電機Taiwan
探索更多
系列:
探索更多
系列: