Thermal Dissipation of PowerStack 250 and 450
"The following table gives typical thermal dissipation as a function of mode of

operation. The models listed below are 120V and 230V versions of PowerStack

250 and 450. On-battery thermal dissipation is given at full rated load over

the entire battery discharge period. Note that on-battery thermal dissipation

is limited in duration according to available battery capacity and output

loading.


ModelOperating On-line
Watts [BTU/Hr]
Operating On-battery
Watts [BTU/Hr]
25016[55]35[120]
45010[34]75[256]
"