What is the maximum inrush current allowed by the ATS48?
Issue:
Specifications for maximum inrush current
Product Line:
Altistart , ATS48
Environment:
All models , all serial numbers
Cause:
Want to increase the current limit on startup.
Resolution:
ATS48 Current limitation setting, will allow up to 700% of the IN (FLA) setting.
Specifications for maximum inrush current
Product Line:
Altistart , ATS48
Environment:
All models , all serial numbers
Cause:
Want to increase the current limit on startup.
Resolution:
ATS48 Current limitation setting, will allow up to 700% of the IN (FLA) setting.
發佈於:施耐德電機Taiwan