Issue:
Does Schneider Electric list the ATV32 maximum duty cycle of the braking transistor?
Product Line:
Altivar 32
Environment:
All models, All serial numbers.
Cause:
Application requiring a braking transistor's continuous use
Resolution:
The braking transistor in the ATV32 series drives is designed to handle Nominal motor power continuously and 150% of nominal motor power for 60 seconds.
An appropriately sized braking resistor must be used that is also capable of handling the required duty cycle.
Does Schneider Electric list the ATV32 maximum duty cycle of the braking transistor?
Product Line:
Altivar 32
Environment:
All models, All serial numbers.
Cause:
Application requiring a braking transistor's continuous use
Resolution:
The braking transistor in the ATV32 series drives is designed to handle Nominal motor power continuously and 150% of nominal motor power for 60 seconds.
An appropriately sized braking resistor must be used that is also capable of handling the required duty cycle.
發佈於:施耐德電機Taiwan

