搜尋常見問題
How can the program be loaded from the EEPROM cartridge to a TSX17?
Issue
How can the program be loaded from the EEPROM cartidge to a TSX17?
Product Line
TSX7 Micro
Environment
TSX17
Resolution
The EEPROM cartridge has a micro switch on it. The micro switch needs to be in the Master (left most) position. With the switch in this position the controller will load from the EEPROM on power up.
發佈於:施耐德電機Taiwan
探索更多
系列:
探索更多
系列: