{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
Why do I receive the error "Incompatibility between the dropped module and the last module of segment 1", when trying to add a module following the STBCPS2111 Auxilliary Power Supply?

The reason this error is received is because when a STBCPS2111 Auxilliary Power Supply is added to the segment it has to be followed by a PDM module and then add a compatible IO module.

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: