{}

我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
搜尋常見問題
How to read energy registers from a CM2xxx series meter?

Issue
How to read energy registers from a CM2000 series meter?

Product Line
CM2000 series meter

Cause 
Customer is having issues reading KWh via modbus registers 

Environment 
CM2000

Resolution
The CM2000 series energy is stored in 4 registers (except Incremental Energy, which is stored in 3 registers). These registers use the Modulo 10,000 format which uses the following formula:
R4*10,000^3 + R3*10,000^2 + R2*10,000 + R1

Details explaining Mod 10k as well as examples can be found in FA212766.

The CM2000 energy registers are listed below as a reference: 
ACCUMULATED ENERGY

1601–1604Real Energy In 3-Phase Total (WH)0 to 9,999,999,999,999,999
1605–1608Reactive Energy In 3-Phase Total (VArH)0 to 9,999,999,999,999,999
1609–1612Real Energy Out 3-Phase Total (WH)0 to 9,999,999,999,999,999
1613–1616Reactive Energy Out 3-Phase Total (VArh)0 to 9,999,999,999,999,999
1617–1620Apparent Energy, 3-Phase Total (VAH)0 to 9,999,999,999,999,999
1621–1624Real Energy Signed/Absolute 3-Phase Total (WH)0 to ±9,999,999,999,999,999
1625–1628Reactive Energy Signed/Absolute 3-Phase Total (VArH)0 to ±9,999,999,999,999,999


CONDITIONAL ACCUMULATED ENERGY

1629–1632Conditional Real Energy In, 3-Phase Total (WH)0 to 9,999,999,999,999,999
1633–1636Conditional Reactive Energy In 3-Phase Total (VArH)0 to 9,999,999,999,999,999
1637–1640Conditional Real Energy Out, 3-Phase Total (WH)0 to 9,999,999,999,999,999
1641–1644Conditional Reactive Energy Out 3-Phase Total (VArH)0 to 9,999,999,999,999,999
1645–1648Conditional Apparent Energy 3-Phase Total (VAH)0 to 9,999,999,999,999,999



INCREMENTAL ACCUMULATED ENERGY

1649–1651Incremental Real Energy In, 3-Phase Total (WH)0 to 999,999,999,999
1652–1654Incremental Reactive Energy In 3-Phase Total (VArH)0 to 999,999,999,999
1655–1657Incremental Real Energy Out, 3-Phase Total (WH)0 to 999,999,999,999
1658–1660Incremental Reactive Energy Out 3-Phase Total (VArH)0 to 999,999,999,999
1661–1663Incremental Apparent Energy 3-Phase Total (VAH)0 to 999,999,999,999

 

施耐德電機Taiwan

探索更多
系列:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.