{}

我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站

搜尋常見問題

Ethernet ports and socket summary on ION meters

Article available in these languages: 西班牙文

Issue
A user would like to know the total allowable simultaneous connections on ION meters

Product Line
ION Meters ( 9000, 8800, 8650/8600, 7650/7550, 7350/7330/7300, 7700, ACM3720) and PM8000

Environment
TCP/IP network sockets

Resolution
The table below summarizes the Ethernet Ports (sockets) available on ION meters
Meter(s)Total Allowable Simultaneous ConnectionsProtocolTCP Port / socketMaximum Connections per Protocol
ION90008 connections total allocated to all protocolsION7700 8
EtherGate (Com1)7801 1
EtherGate (Com4)7802 1
DNP20000 3
IEC 61850102 5
Modbus TCP502 8
Modbus RTU7701 8
Telnet23 1
FTP21 2
Webserver (HTTP)80 10
Secure webserver (HTTPS)443 10
PM80008 connections total allocated to all protocolsION7700 8
EtherGate COM17801 1
DNP 3.020000 3
IEC 61850102 5
Modbus TCP502 32
Modbus RTU7701 4
Telnet23 1
FTP21 1
Web server (HTTP)80 1
ION 86508 connections total allocated to all protocolsION7700 8
EtherGate COM17801 1
EtherGate COM47802 1
DNP 3.020000 3
IEC 61850102 5
Modbus TCP502 8
Modbus RTU7701 8
Telnet23 1
FTP21 1
Web server (HTTP)80 1
ION 8600(V330)
, 8800(V334)
4 connections total allocated to all the protocolsION7700 4
Modbus RTU7701 4
Modbus TCP502 4
EtherGate COM17801 1
EtherGate COM27802 1
Telnet23 1
DNP20000 3
Modbus Master502 10
ION 7500, 7550*
7600, 7650*
8300, 8400 8500
* Firmware revisions prior to V350
4 connections total allocated to all the protocolsION7700 4
Modbus RTU7701 4
Modbus TCP502 4
EtherGate COM17801 1
EtherGate COM27802 1
Telnet23 1
ION 7550*, 7650*
With V350 Firmware
4 pooled socket connections in total allocated to all the protocolsION7700 4
Modbus RTU7701 4
EtherGate COM17801 1
EtherGate COM27802 1
Telnet23 1
DNP20000 3
Modbus TCP*502 32
ION 7700 / Xpress Card1 max connection from either: ION or Modbus RTU.
1 max telnet session, independent of other connections.
ION7700 1
Modbus RTU7700 1
EtherGate COM2 and COM3 simultaneously7800 1
EtherGate COM2 only7802 1
EtherGate COM3 only7803 1
Telnet23 1
ION 7300, 7330, 7350-1 max dedicated ethergate connection
-1 max connection from either: Telnet, ION Modbus RTU or Modbus TCP
- The EtherGate and ION/etc connections are independent of each other (i.e. not pooled together)
ION7700 1
Modbus RTU7701 1
ModBus TCP502 1
EtherGate - COM27802 1
Telnet23 1
ACM 37203720 Protocol3721 1 to 3
Modbus RTU3722 1 to 3
Telnet23 1

施耐德電機Taiwan

探索更多
系列:
探索更多
系列: